Publicación: Desarrollo de una herramienta para la evaluacion de la eficiencia de una torre de enfriamiento de agua
| dc.contributor.advisor | Barajas Ferreira, Crisostomo | |
| dc.contributor.advisor | Forero Sanabria, Jorge Enrique | |
| dc.contributor.author | Calderon Godoy, Blanca Johana | |
| dc.contributor.author | Pinto Galvis, Helmer Geobel | |
| dc.date.accessioned | 2024-03-03T04:35:59Z | |
| dc.date.available | 2004 | |
| dc.date.available | 2024-03-03T04:35:59Z | |
| dc.date.created | 2004 | |
| dc.date.issued | 2004 | |
| dc.description.abstract | La herramienta propuesta permite el cálculo del perfil de temperatura para el agua, el perfil de temperatura para el aire, el perfil de humedad y la demanda térmica a contracorriente en una torre de enfriamiento de agua de tiro inducido a contracorriente. Como un primer paso, se construye un modelo matemático, que rige el funcionamiento de una torre de enfriamiento de agua de tiro inducido a contracorriente que contiene un empaque de madera vertical. El modelo matemático estructurado contiene ecuaciones que describen los fenómenos de transferencia de masa, transferencia de calor , el balance de energía y la ecuación de equilibrio generada a partir de datos para el sistema aire-agua reportados en la literatura. En el modelo también se incluyen ecuaciones que modelan el comportamiento termodinámico de la torre partiendo de datos de entalpía de la mezcla aire-vapor de agua a 1 atmósfera de presión. Una vez conformado el modelo, este se resuelve numéricamente para cada uno de los empaques utilizados partiendo de las mismas condiciones de operación y diseño con el fin de obtener los resultados del modelo operacional, luego se obtiene la demanda térmica a contracorriente a partir de las condiciones de diseño. Por último, se generan diferentes datos de condiciones de operación con el fin de evaluar la demanda térmica a contracorriente para la herramienta y para el demo CTI Toolkit de Cooling Tower Institute. De la solución numérica se obtuvo el calor removido por la torre, el porcentaje de agua perdido, la temperatura de agua fría, la temperatura del aire a la salida, la demanda térmica a contracorriente, los perfiles de temperatura para el agua y el aire y el perfil de humedad. Además, se obtiene que el empaque más eficiente es el de madera vertical y que la herramienta tiene una confiabilidad del 98% al compararla con el demo CTI Toolkit de Cooling Tower Institute. | |
| dc.description.abstractenglish | The proposed tool permits the calculation of the temperature profile for water, the temperatureprofile for air, the humidity profile and the thermal demand to counterstream in a induced shot tocounterstream water-cooling tower. As a first sep, a mathematical model wich rules the functionig of induced shot to counterstreamwater-cooling tower which countains a wooden vertical seal-is constructed. The structuredmathematical model contains equations describing the phenomena of mass transference, heattransference, energy balance and the equation of generated equilibrium from reported-in-literaturedata for the air-water system. Equations modeling the thermodynamic behavior of the tower startingfrom data of entalpy from the mixture air-water steam at a presure or 1 atmosphere are included inthe in the model. Once the model is constituted, it is numerically solved for each of the utilized seals starting from thesame conditions of operation and desing with the purpose of obtaining the results of the operationalmodel, then the thermal demand to counterstream according to the conditions of design. Finally,several data about the conditions of operation are generated with the purpose of evaluatig thethermal demand at counterstream for the tool and for demo “CTI Toolkit” from the Cooling TowerInstitute. From the numeric solution the removed heat of the tower is obtained, the porcentage of lost waterthe temperature of cold water, the air temperature in the exit, the thermal demand to counterstream,the temperature porfiles for water and air the humidity profile were obtained. Also, it is obtained thatthe most eficient seal is the wooden vertical one and that the tool has a reliability of 98%, whencomparing it with demo “CTI Toolkit’ from Cooling Tower Institute. “ Grade thesis.' Faculty of Physicochemical Engineering. Department of Chemical Engineering. Chaiman. M. Sc.Criséstomo Barajas | |
| dc.description.degreelevel | Pregrado | |
| dc.description.degreename | Ingeniero Químico | |
| dc.format.mimetype | application/pdf | |
| dc.identifier.instname | Universidad Industrial de Santander | |
| dc.identifier.reponame | Universidad Industrial de Santander | |
| dc.identifier.repourl | https://noesis.uis.edu.co | |
| dc.identifier.uri | https://noesis.uis.edu.co/handle/20.500.14071/16099 | |
| dc.language.iso | spa | |
| dc.publisher | Universidad Industrial de Santander | |
| dc.publisher.faculty | Facultad de Ingenierías Fisicoquímicas | |
| dc.publisher.program | Ingeniería Química | |
| dc.publisher.school | Escuela de Ingeniería Química | |
| dc.rights | http://creativecommons.org/licenses/by/4.0/ | |
| dc.rights.accessrights | info:eu-repo/semantics/openAccess | |
| dc.rights.creativecommons | Atribución-NoComercial-SinDerivadas 4.0 Internacional (CC BY-NC-ND 4.0) | |
| dc.rights.license | Attribution-NonCommercial 4.0 International (CC BY-NC 4.0) | |
| dc.rights.uri | http://creativecommons.org/licenses/by-nc/4.0 | |
| dc.subject | Torre de enfriamiento | |
| dc.subject | Tiro inducido | |
| dc.subject | Modelo operacional | |
| dc.subject | Modelo termodinámico | |
| dc.subject | Matlab | |
| dc.subject | Labview. | |
| dc.subject.keyword | Cooling tower | |
| dc.subject.keyword | Induced shot | |
| dc.subject.keyword | Operational model | |
| dc.subject.keyword | Thermodynamic model | |
| dc.subject.keyword | Matlab.Labview. | |
| dc.title | Desarrollo de una herramienta para la evaluacion de la eficiencia de una torre de enfriamiento de agua | |
| dc.title.english | Developing a tool for evaluating the eficiency of a water-cooling tower. | |
| dc.type.coar | http://purl.org/coar/version/c_b1a7d7d4d402bcce | |
| dc.type.hasversion | http://purl.org/coar/resource_type/c_7a1f | |
| dc.type.local | Tesis/Trabajo de grado - Monografía - Pregrado | |
| dspace.entity.type | Publication |