Prueba para implementación de dióxido de cloro en el sistema de tratamiento de agua de la compañía eléctrica sochagota para el control de manganeso y cloruros
dc.contributor.advisor | Gauthier, Gilles Henri | |
dc.contributor.advisor | Rodriguez, Jose Herney | |
dc.contributor.author | Bravo Mejia, Laura Marcela | |
dc.date.accessioned | 2023-04-06T14:46:29Z | |
dc.date.available | 2023 | |
dc.date.available | 2023-04-06T14:46:29Z | |
dc.date.created | 2019 | |
dc.date.issued | 2019 | |
dc.description.abstract | Durante los últimos años, las actividades de inspección de las instalaciones de la compañía eléctrica Sochagota evidenciaron la formación de películas de ensuciamiento sobre las superficies de algunos equipos, principalmente en los sistemas de enfriamiento y clarificación de agua. Este tipo de ensuciamiento ocasiona problemas como corrosión, disminución en la eficiencia del sistema de enfriamiento, aumento en el requerimiento de agua de enfriamiento, crecimiento de microorganismos, entre otros. Los resultados de análisis realizados a estas películas indican que su composición en gran parte es manganeso como óxido proveniente del agua del río Chicamocha, la cual es empleada en el proceso de clarificación. Los altos niveles de contaminación del agua de este río se deben principalmente al vertimiento de las aguas residuales provenientes de los municipios aledaños, la cárcel de Combita, y pequeñas industrias cercanas. Debido a las altas concentraciones de manganeso, el oxidante comúnmente empleado en el tratamiento de agua no logra remover este metal hasta el valor objetivo (0,03 ppm) y además genera iones cloruro que se concentran rápidamente en la torre de enfriamiento superando el valor permitido, por tal razón, parte de este continúa hacia el sistema de enfriamiento, donde se concentra aún más debido a la constante evaporación, recirculación y reposición de agua en la balsa de la torre. Como una alternativa para aumentar la remoción de manganeso, se emplea ClO2 como oxidante en el sistema de clarificación durante una prueba de campo. El seguimiento realizado durante este tiempo evidenció que aun cuando fue necesario incrementar la demanda de Dióxido de Cloro establecida mediante las pruebas a nivel de laboratorio debido a la baja eficiencia del generador, el nivel de manganeso se mantuvo por debajo del límite definido y además se redujo la concentración de cloruros tanto en el agua tratada como en la torre de enfriamiento. | |
dc.description.abstractenglish | On recent years, the compania electrica Sochagota’s facility inspection activities showed the formation of soiling films on some equipment surfaces, mainly on the cooling and clarification systems. This type of soiling causes problems such as corrosion, cooling system’s decrease in efficiency, increase in the cooling water demand, growth of microorganisms, among others. The results of the analysis made to these films indicate that its composition is mainly manganese as oxide coming from water of Chicamocha river, which is used in the clarification process. This river’s high levels of water contamination are mainly due to wastewater dumping from neighboring towns, Combita’s jail and nearby small industries. Due to high manganese concentrations, the oxidizer commonly used on water treatment, does not manage to remove this metal to the goal value (0,03 ppm) and in addition it generates chloride ions that concentrate quickly in the cooling tower exceeding the allowed value, for that reason, part of it goes towards the cooling system, where it concentrates even more due to the constant evaporation, recirculation and water replenishment in the tower raft. As an alternative to increase the removal of manganese, ClO2 is used as an oxidant in the clarification system during a field test. The follow-up during this time showed that even when it was necessary to increase the Chlorine Dioxide demand established through laboratory tests due to low generator efficiency, manganese level remained below the defined limit and also reduced chlorides concentration in both treated water and cooling tower | |
dc.description.degreelevel | Pregrado | |
dc.description.degreename | Ingeniero Químico | |
dc.format.mimetype | application/pdf | |
dc.identifier.instname | Universidad Industrial de Santander | |
dc.identifier.reponame | Universidad Industrial de Santander | |
dc.identifier.repourl | https://noesis.uis.edu.co | |
dc.identifier.uri | https://noesis.uis.edu.co/handle/20.500.14071/13727 | |
dc.language.iso | spa | |
dc.publisher | Universidad Industrial de Santander | |
dc.publisher.faculty | Facultad de Ingenierías Fisicoquímicas | |
dc.publisher.program | Ingeniería Química | |
dc.publisher.school | Escuela de Ingeniería Química | |
dc.rights | info:eu-repo/semantics/openAccess | |
dc.rights.accessrights | info:eu-repo/semantics/openAccess | |
dc.rights.coar | http://purl.org/coar/access_right/c_abf2 | |
dc.rights.creativecommons | Atribución-NoComercial-SinDerivadas 4.0 Internacional (CC BY-NC-ND 4.0) | |
dc.rights.license | Attribution-NonCommercial 4.0 International (CC BY-NC 4.0) | |
dc.rights.uri | http://creativecommons.org/licenses/by-nc-nd/4.0/ | |
dc.subject | Ensuciamiento | |
dc.subject | Sistema De Enfriamiento | |
dc.subject | Manganeso | |
dc.subject | Clarificación | |
dc.subject | Clo2. | |
dc.subject.keyword | Soiling | |
dc.subject.keyword | Cooling System | |
dc.subject.keyword | Manganese | |
dc.subject.keyword | Clarification | |
dc.subject.keyword | Clo2. | |
dc.title | Prueba para implementación de dióxido de cloro en el sistema de tratamiento de agua de la compañía eléctrica sochagota para el control de manganeso y cloruros | |
dc.title.english | Test for chlorine dioxide implementation in the campania manganese and chloride control. * | |
dc.type.coar | http://purl.org/coar/version/c_b1a7d7d4d402bcce | |
dc.type.hasversion | http://purl.org/coar/resource_type/c_7a1f | |
dc.type.local | Tesis/Trabajo de grado - Monografía - Pregrado | |
dspace.entity.type |
Files
Original bundle
1 - 3 of 3
No Thumbnail Available
- Name:
- Carta de autorización.pdf
- Size:
- 405.74 KB
- Format:
- Adobe Portable Document Format
No Thumbnail Available
- Name:
- Nota de proyecto.pdf
- Size:
- 130.6 KB
- Format:
- Adobe Portable Document Format