Calculation of indirect-lightning flashover rate on distribution lines from indirect lightning in tropical zones
dc.creator | Soto Ríos, Edison | |
dc.creator | Pérez-González, Ernesto | |
dc.creator | Trujillo, Diego del Río | |
dc.date | 2018-01-12 | |
dc.date.accessioned | 2022-03-14T20:29:53Z | |
dc.date.available | 2022-03-14T20:29:53Z | |
dc.description | In this paper the indirect-lightning flashover rate of a distribution line is obtained following the procedure described in the IEEE Std. 1410 – 2010, but using other parameters of the first stroke distributions (peak current and front time) adopted by CIGRÉ. These parameters were taken from the measured currents of the Morro do Cachimbo Station in Belo Horizonte – Brazil, which are representative of the tropical zone. As a result, the calculated flashover rate with the data of tropical zone is higher than one obtained with the CIGRÉ curves. Such increments could be in the most extreme case of 70%. | en-US |
dc.description | En este artículo se obtiene el índice de fallas por impactos indirectos de una línea de distribución siguiendo el procedimiento descrito en el estándar IEEE 1410 de 2010, pero cambiando los parámetros de las distribuciones de la primera descarga de retorno (corriente pico y tiempo de frente) adoptados por CIGRÉ por los obtenidos de 38 mediciones de corrientes en la estación experimental del Morro do Cachimbo en Belo Horizonte – Brasil, que son representativas de la zona tropical. Se encuentra como resultado que la tasa de fallas calculada con los datos de zona tropical es mayor a los que se obtienen con las curvas del CIGRÉ. Dichos incrementos pueden ser en el caso más extremo de hasta 70%. | es-ES |
dc.format | application/pdf | |
dc.format | text/html | |
dc.identifier | https://revistas.uis.edu.co/index.php/revistauisingenierias/article/view/7666 | |
dc.identifier | 10.18273/revuin.v17n1-2018021 | |
dc.identifier.uri | https://noesis.uis.edu.co/handle/20.500.14071/8422 | |
dc.language | spa | |
dc.publisher | Universidad Industrial de Santander | es-ES |
dc.relation | https://revistas.uis.edu.co/index.php/revistauisingenierias/article/view/7666/7923 | |
dc.relation | https://revistas.uis.edu.co/index.php/revistauisingenierias/article/view/7666/9407 | |
dc.rights | Derechos de autor 2018 Revista UIS Ingenierías | es-ES |
dc.rights.accessrights | info:eu-repo/semantics/openAccess | |
dc.rights.coar | http://purl.org/coar/access_right/c_abf2 | |
dc.rights.creativecommons | Atribución-NoComercial-SinDerivadas 4.0 Internacional (CC BY-NC-ND 4.0) | |
dc.rights.license | Attribution-NonCommercial 4.0 International (CC BY-NC 4.0) | |
dc.source | REVISTA UIS ENGENHARIAS; v. 17 n. 1 (2018): Revista UIS Ingenierías; 217-222 | pt-BR |
dc.source | Revista UIS Ingenierías; Vol. 17 Núm. 1 (2018): Revista UIS Ingenierías; 217-222 | es-ES |
dc.source | Revista UIS Ingenierías; Vol. 17 No. 1 (2018): Revista UIS Ingenierías; 217-222 | en-US |
dc.source | 2145-8456 | |
dc.source | 1657-4583 | |
dc.subject | Lightning parameters | en-US |
dc.subject | flashover rate | en-US |
dc.subject | distribution lines | en-US |
dc.subject | lightning induced voltages | en-US |
dc.subject | CIGRÉ | en-US |
dc.subject | MCS | en-US |
dc.subject | Parámetros del rayo | es-ES |
dc.subject | índice de fallas | es-ES |
dc.subject | líneas de distribución | es-ES |
dc.subject | tensiones inducidas | es-ES |
dc.subject | CIGRÉ | es-ES |
dc.subject | MCS | es-ES |
dc.title | Calculation of indirect-lightning flashover rate on distribution lines from indirect lightning in tropical zones | en-US |
dc.title | Obtención del índice de fallas de líneas de distribución ante impactos indirectos de rayo en zona tropical | es-ES |
dc.type | info:eu-repo/semantics/article | |
dc.type | info:eu-repo/semantics/publishedVersion | |