Diseño e Ingeniería Conceptual para el Sistema de Protección Contraincendio de los Recipientes de Almacenamiento de Hidrocarburos Livianos de la Unidad de Craqueo Catalítico UOP I

dc.contributor.advisorBarajas Ferreira, Crisóstomo
dc.contributor.advisorMuñóz Baquero, Diego Fernando
dc.contributor.authorRamírez Restrepo, Jorge Iván
dc.contributor.authorSanguino Rodríguez, Edwin José
dc.contributor.evaluatorGuerrero Amaya, Hernando
dc.contributor.evaluatorPedraza Avella, Julio Andres
dc.date.accessioned2022-09-16T13:00:53Z
dc.date.available2022-09-16T13:00:53Z
dc.date.created2022-09-07
dc.date.issued2022-09-07
dc.description.abstractLas unidades de cracking, VRU, Etano-etileno y amina, son plantas las cuales manejan y procesan productos derivados del petróleo, altamente inflamables y combustibles, los cuales generan un alto riesgo de explosión e incendio dentro de las instalaciones. Algunos de estos fluidos tienen composiciones asimilables al gas licuado de petróleo (GLP) por lo que presentan riesgos potenciales de generar explosiones tipo BLEVE (boiling liquid expanding vapour explosion) que llevan a la escalación de incendios a los bloques de planta anexos. Por esta razón, para algunos equipos se utilizaron criterios de protección tomados del API 2510 A “Fire protection considerations for the design and operation of liquefied petroleum gas (LPG) storage facilities”. Además de los incendios tipo BLEVE, se pueden anticipar incendios tipo “jet” debido a que la presión en casi todos los casos supera las 50 psig. Debido a la cercanía entre equipos a proteger según el reporte de Arthur D’ Little (ADL) de otros cuya protección no se solicita en el estudio, se toma como área potencial de incendio la que incluye los equipos alrededor de los que se deben proteger dentro de un área de 15m x 15m (criterio API STD 521 “Guide for Pressure-relieving and Depressuring Systems). De esta manera, toda la planta se ha dividido en secciones protegidas por válvulas de diluvio automáticas. Esta ingeniería contempla las modificaciones del sistema de protección contra incendios de la unidad U-2700 requeridas para resolver las recomendaciones generadas por el estudio realizado por Arthur D’ Little (ADL), en las cuales se exponen los diferentes riesgos asociados a la pérdida de contención e incendio dentro de las instalaciones de la planta. El análisis de la información se llevó a cabo siguiendo los lineamientos de las técnicas de gestión de peligros y riesgos aprobadas por Ecopetrol S.A. los cuales son descritos en el desarrollo este trabajo. La modelación hidráulica de los nodos y lazos de suministro de agua para la protección de los equipos críticos se realizó por medio de un Software llamado EPANET 2.0.
dc.description.abstractenglishThe cracking units, VRU, Ethane-ethylene and amine, are plants which handle and process highly flammable and combustible petroleum products, which generate a high risk of explosion and fire within the facilities. Some of these fluids have compositions that can be assimilated to liquefied petroleum gas (LPG), which is why they present potential risks of generating BLEVE (boiling liquid expanding vapor explosion) type explosions that lead to the escalation of fires to the adjacent plant blocks. For this reason, protection criteria taken from API 2510 A “Fire protection considerations for the design and operation of liquefied petroleum gas (LPG) storage facilities” were used for some equipment. In addition to BLEVE type fires, “jet” type fires can be anticipated because the pressure in almost all cases exceeds 50 psig. Due to the proximity between equipment to be protected according to the report by Arthur D'Little (ADL) of others whose protection is not requested in the study, the potential fire area is taken to include the equipment around which it must be protected within of an area of 15m x 15m (API STD 521 “Guide for Pressure-relieving and Depressuring Systems”). In this way, the entire plant has been divided into sections protected by automatic deluge valves. This engineering contemplates the modifications of the fire protection system of unit U-2700 required to resolve the recommendations generated by the study carried out by Arthur D' Little (ADL), in which the different risks associated with the loss of containment are exposed. and fire inside the plant facilities. The analysis of the information was carried out following the guidelines of the hazard and risk management techniques approved by Ecopetrol S.A. which are described in the development of this work. The hydraulic modeling of the nodes and water supply loops for the protection of critical equipment was carried out using software called EPANET 2.0.
dc.description.degreelevelPregrado
dc.description.degreenameIngeniero de Procesos de Refinación y Petroquímicos
dc.format.mimetypeapplication/pdf
dc.identifier.instnameUniversidad Industrial de Santander
dc.identifier.reponameUniversidad Industrial de Santander
dc.identifier.repourlhttps://noesis.uis.edu.co
dc.identifier.urihttps://noesis.uis.edu.co/handle/20.500.14071/11467
dc.language.isospa
dc.publisherUniversidad Industrial de Santander
dc.publisher.facultyFacultad de Ciencias Humanas
dc.publisher.programIngeniería de Procesos de Refinación y Petroquímicos
dc.publisher.schoolEscuela de Ingeniería Química
dc.rightsinfo:eu-repo/semantics/openAccess
dc.rights.accessrightsinfo:eu-repo/semantics/openAccess
dc.rights.coarhttp://purl.org/coar/access_right/c_abf2
dc.rights.creativecommonsAtribución-NoComercial-SinDerivadas 4.0 Internacional (CC BY-NC-ND 4.0)
dc.rights.licenseAttribution-NonCommercial 4.0 International (CC BY-NC 4.0)
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/4.0/
dc.titleDiseño e Ingeniería Conceptual para el Sistema de Protección Contraincendio de los Recipientes de Almacenamiento de Hidrocarburos Livianos de la Unidad de Craqueo Catalítico UOP I
dc.title.englishDesign and Conceptual Engineering for the Fire Protection System for the Storage Vessels of Light Hydrocarbons of the Catalytic Cracking Unit UOP I
dc.type.coarhttp://purl.org/coar/resource_type/c_7a1f
dc.type.hasversionhttp://purl.org/coar/version/c_b1a7d7d4d402bcce
dc.type.localTesis/Trabajo de grado - Monografía - Pregrado
dspace.entity.type
Files
Original bundle
Now showing 1 - 3 of 3
No Thumbnail Available
Name:
Carta de autorización.pdf
Size:
7.22 MB
Format:
Adobe Portable Document Format
No Thumbnail Available
Name:
Nota de proyecto.pdf
Size:
662.42 KB
Format:
Adobe Portable Document Format
Loading...
Thumbnail Image
Name:
Documento.pdf
Size:
3.92 MB
Format:
Adobe Portable Document Format
License bundle
Now showing 1 - 1 of 1
No Thumbnail Available
Name:
license.txt
Size:
2.18 KB
Format:
Item-specific license agreed to upon submission
Description: