Logotipo del repositorio

Publicación:
Estrategia de control local tensión-reactiva en sistemas de distribución a partir de bancos de capacitores y cambia tomas en transformadores utilizando aprendizaje por refuerzo

dc.contributor.advisorCESAR ANTONIO DUARTE GUALDRON
dc.contributor.advisorALAN FERNEY LIZARAZO MALDONADO
dc.contributor.authorALVAREZ CASTILLO AURELIO ARTUR
dc.contributor.authorCAMPOS SOTO JULIAN DAVID
dc.contributor.evaluatorCESAR AUGUSTO OROZCO HENAO
dc.contributor.evaluatorCAMILO ESTEBAN CARRILLO VALERA
dc.date.accessioned2026-06-12T19:57:59Z
dc.date.created2026-06-09
dc.date.issued2026-06-09
dc.description.abstractEl control tensión-reactiva (Volt/Var Control, VVC) es una función esencial para mantener la calidad del servicio en redes de distribución, especialmente ante la creciente variabilidad introducida por cambios en la demanda y la incorporación de recursos energéticos distribuidos. En este trabajo se evalúa una estrategia de control local basada en aprendizaje profundo por refuerzo para coordinar dispositivos discretos convencionales en una red de distribución. La propuesta utiliza un esquema Multi-Agent Soft Actor-Critic (MSAC) con entrenamiento centralizado y ejecución descentralizada, de manera que cada dispositivo decide con información local durante la operación, mientras que la coordinación entre agentes se favorece durante el aprendizaje. La metodología se implementa sobre el alimentador IEEE de 33 nodos en pandapower, con un transformador OLTC y siete bancos de capacitores, representados mediante ocho agentes. Cada actor observa variables locales de tensión, potencia activa, potencia reactiva y estado del actuador, mientras que los críticos emplean información global del sistema y la acción conjunta. La función de recompensa penaliza las violaciones de tensión fuera de la banda operativa y el consumo de potencia aparente en la barra slack. El desempeño del método se compara con un esquema centralizado basado en Discrete Coordinate Descent (DCD) y se evalúa tanto en un escenario nominal como en escenarios estocásticos generados con distribución de Weibull. Los resultados muestran que, en condiciones nominales, el MSAC elimina las violaciones de tensión observadas en el caso base y mejora el comportamiento operativo del sistema. Frente al método DCD, el MSAC ofrece un mejor control del perfil de tensión, mientras que el DCD presenta mayor eficiencia en la reducción de la potencia aparente global. En escenarios con certidumbre elevada, el desempeño del control local se degrada, lo que evidencia que la estrategia propuesta es prometedora para condiciones predecibles, pero requiere mecanismos adicionales de robustez para operar con alta variabilidad.
dc.description.abstractenglishVolt/Var Control (VVC) is a key function for maintaining service quality in distribution networks, particularly under increasing variability caused by load fluctuations and the growing penetration of distributed energy resources. This work evaluates a local control strategy based on Deep Reinforcement Learning for coordinating conventional discrete devices in a distribution system. The proposed approach relies on a Multi-Agent Soft Actor-Critic (MSAC) framework with centralized training and decentralized execution, so that each device operates with local information during real-time execution, while coordination among agents is promoted during training. The methodology is implemented on the IEEE 33-bus feeder in pandapower, using one OLTC transformer and seven capacitor banks, represented as eight agents. Each actor observes local voltage, active power, reactive power, and actuator state variables, whereas the critics receive global system information together with the joint action. The reward function penalizes voltage violations outside the admissible band and the apparent power drawn from the slack bus. The proposed method is compared against a centralized Discrete Coordinate Descent (DCD) strategy and is assessed under both a nominal operating scenario and stochastic scenarios generated through a Weibull-based model. The results show that, under nominal conditions, MSAC removes the voltage violations observed in the base case and improves the overall operating behavior of the system. When compared with DCD, MSAC provides better voltage-profile regulation, whereas DCD achieves greater efficiency in reducing global apparent power demand. Under high-uncertainty scenarios, the performance of the local control strategy deteriorates, indicating that the proposed approach is promising for predictable operating conditions but still requires additional robustness echanisms to cope with highly variable environments.
dc.description.degreelevelPregrado
dc.description.degreenameIngeniero Electricista
dc.format.mimetypeapplication/pdf
dc.identifier.instnameUniversidad Industrial de Santander
dc.identifier.reponameUniversidad Industrial de Santander
dc.identifier.repourlhttps://noesis.uis.edu.co
dc.identifier.urihttps://noesis.uis.edu.co/handle/20.500.14071/47944
dc.language.isospa
dc.publisherUniversidad Industrial de Santander
dc.publisher.facultyFacultad de Ingeníerias Fisicomecánicas
dc.publisher.programIngeniería Eléctrica
dc.publisher.schoolEscuela de Ingenierías Eléctrica, Electrónica y Telecomunicaciones
dc.rightsinfo:eu-repo/semantics/openAccess
dc.rights.accessrightsinfo:eu-repo/semantics/openAccess
dc.rights.coarhttp://purl.org/coar/access_right/c_abf2
dc.rights.creativecommonsAtribución-NoComercial-SinDerivadas 4.0 Internacional (CC BY-NC-ND 4.0)
dc.rights.licenseAttribution-NonCommercial 4.0 International (CC BY-NC 4.0)
dc.rights.urihttps://creativecommons.org/licenses/by-nd/4.0/
dc.subjectcontrol tensión-reactiva
dc.subjectaprendizaje profundo por refuerzo
dc.subjectSoft Actor-Critic
dc.subjectsistemas multiagente
dc.subjectredes de distribución
dc.subjectbancos de capacitores
dc.subjectOLTC.
dc.subject.keyworddeep reinforcement learning
dc.subject.keywordSoft Actor-Critic
dc.subject.keywordmulti-agent systems
dc.subject.keyworddistribution networks
dc.subject.keywordcapacitor banks
dc.subject.keywordOLTC.
dc.subject.keywordVolt/Var control
dc.titleEstrategia de control local tensión-reactiva en sistemas de distribución a partir de bancos de capacitores y cambia tomas en transformadores utilizando aprendizaje por refuerzo
dc.title.englishLocal Volt-VAR Control Strategy in Distribution Systems Using Capacitor Banks and Transformer Tap Changers via Reinforcement Learning
dc.type.coarhttp://purl.org/coar/resource_type/c_7a1f
dc.type.hasversionhttp://purl.org/coar/version/c_b1a7d7d4d402bcce
dc.type.localTesis/Trabajo de grado - Monografía - Pregrado
dspace.entity.typePublication

Archivos

Bloque original

Mostrando 1 - 4 de 4
Cargando...
Miniatura
Nombre:
Nota de proyecto.pdf
Tamaño:
257.26 KB
Formato:
Adobe Portable Document Format
Cargando...
Miniatura
Nombre:
Apéndices.zip
Tamaño:
22.42 MB
Formato:
Unknown data format
Cargando...
Miniatura
Nombre:
Carta de autorizacion.pdf
Tamaño:
283.54 KB
Formato:
Adobe Portable Document Format
Cargando...
Miniatura
Nombre:
Documento.pdf
Tamaño:
2.57 MB
Formato:
Adobe Portable Document Format

Bloque de licencias

Mostrando 1 - 1 de 1
Cargando...
Miniatura
Nombre:
license.txt
Tamaño:
2.17 KB
Formato:
Item-specific license agreed to upon submission
Descripción:

VIGILADA MINEDUCACIÓN

Ordenanza No. 83 de 1.944 (junio 22)

Carácter académico: Universidad

Notificaciones judiciales: notjudiciales@uis.edu.co 

.

Código SNIES: 1204   Nit: 890.201.213-4

Línea Anticorrupción:  +57 (601) 562 9300 EXT: 3633

Línea transparente: +57 (607) 630 3031