Publicación: Diseño y construcción de un banco para el análisis del comportamiento de un sistema de refrigeración implementando un mecanismo de control continuo
| dc.contributor.advisor | Gelvez Arocha, Omar Armando | |
| dc.contributor.author | Duran Mantilla, Juan Mateo | |
| dc.contributor.author | Mora Garces, Juan Carlos | |
| dc.date.accessioned | 2024-03-03T23:14:03Z | |
| dc.date.available | 2017 | |
| dc.date.available | 2024-03-03T23:14:03Z | |
| dc.date.created | 2017 | |
| dc.date.issued | 2017 | |
| dc.description.abstract | En la actualidad, ante el panorama energético mundial que exige la optimización de la energía empleada en cualquier sistema, resulta imprescindible que un ingeniero mecánico conozca y comprenda las estrategias de control contínuo utilizadas en los sistemas de refrigeración, sus ventajas y desventajas. Para ello, se diseñó y construyó un banco experimental equipado con un compresor inverter y una interfaz gráfica donde los estudiantes pueden analizar y observar el comportamiento y operación de un sistema de refrigeración operando según esquemas de control ON-OFF, PID Y Fuzzy. El prototipo construido consta de cuatro subsistemas: refrigeración, simulación de carga, control y adquisición de datos y estructura de soporte. Cada uno de los elementos que conforman dichos subsistemas fue dimensionado y seleccionado acorde con los requerimientos planteados. Un procedimiento de cálculo para la longitud de tubos capilares y un método de dimensionamiento para evaporadores basado en correlaciones experimentales de flujo bifásico fueron desarrollados como parte del proceso de diseño. Los algoritmos de control se operan a través de un software programado en LabVIEW que varía la velocidad de un compresor inverter en función de la carga térmica, la cual es impuesta al sistema por agua que puede ser calentada a través de tres resistencias sumergidas que inducen las perturbaciones. Parámetros como la capacidad del condensador, la carga térmica y la velocidad del compresor fueron variados para estudiar el comportamiento del sistema y el impacto que estos tienen en su desempeño. Los resultados experimentales de la comparación del consumo energético para cada estrategia de control muestran que los controladores continuos ofrecen un ahorro considerable respecto a los controladores ON-OFF y se encontró que el controlador Fuzzy registra un ahorro energético mayor que el PID. (*) | |
| dc.description.abstractenglish | In present times, given the energetic situation in the world that demands the optimum use of energy in any system, it is essential that any mechanical engineer know and comprehend the control strategies used in refrigeration systems as well as their advantages and disadvantages. An experimental bench equipped with an inverter compressor and a graphic interface was designed and built where the students can visualize and analyze the behavior and operation of a refrigeration system working under ON-OFF, PID and Fuzzy control schemes. The prototype consists of four sub-systems: refrigeration, load simulation, control and data acquisition and supporting structure. All the elements that conform the sub-systems were sized and selected according with the established requirements. A calculation procedure for capillary tube length and an evaporator sizing method based on experimental biphasic flow correlations were developed as part of the design process. The control algorithms are operated through a software programmed using LabVIEW that regulates the compressor speed depending on the thermal load which is simulated by the action of three electrical resistors that are submerged in water that flows through the evaporator. Parameters as the condenser capacity, thermal load and compressor speed were varied to study the impact of each of them in the system performance. The experimental results of the energy consumption comparison between each control strategy show that the continuous control strategies offer a substantial energy save regarding ON-OFF controllers and It was found that the Fuzzy controller exhibits a greater energy saving in comparison with PID. (*) | |
| dc.description.degreelevel | Pregrado | |
| dc.description.degreename | Ingeniero Mecánico | |
| dc.format.mimetype | application/pdf | |
| dc.identifier.instname | Universidad Industrial de Santander | |
| dc.identifier.reponame | Universidad Industrial de Santander | |
| dc.identifier.repourl | https://noesis.uis.edu.co | |
| dc.identifier.uri | https://noesis.uis.edu.co/handle/20.500.14071/35727 | |
| dc.language.iso | spa | |
| dc.publisher | Universidad Industrial de Santander | |
| dc.publisher.faculty | Facultad de Ingenierías Fisicomecánicas | |
| dc.publisher.program | Ingeniería Mecánica | |
| dc.publisher.school | Escuela de Ingeniería Mecánica | |
| dc.rights | http://creativecommons.org/licenses/by/4.0/ | |
| dc.rights.accessrights | info:eu-repo/semantics/openAccess | |
| dc.rights.creativecommons | Atribución-NoComercial-SinDerivadas 4.0 Internacional (CC BY-NC-ND 4.0) | |
| dc.rights.license | Attribution-NonCommercial 4.0 International (CC BY-NC 4.0) | |
| dc.rights.uri | http://creativecommons.org/licenses/by-nc/4.0 | |
| dc.subject | Refrigeración | |
| dc.subject | Control On-Off | |
| dc.subject | Control Pid | |
| dc.subject | Control Fuzzy | |
| dc.subject | Banco Experimental | |
| dc.subject | Compresor Inverter | |
| dc.subject | Consumo Energético | |
| dc.subject | Eficiencia. | |
| dc.subject.keyword | Refrigeration | |
| dc.subject.keyword | On-Off Controller | |
| dc.subject.keyword | Pid Controller | |
| dc.subject.keyword | Fuzzy Controller | |
| dc.subject.keyword | Experimental Bench | |
| dc.subject.keyword | Inverter Compressor | |
| dc.subject.keyword | Energy Consumption | |
| dc.subject.keyword | Efficiency. | |
| dc.title | Diseño y construcción de un banco para el análisis del comportamiento de un sistema de refrigeración implementando un mecanismo de control continuo | |
| dc.title.english | Design and construction of an experimental bench for operation analysis of a refrigeration system using a continuous control mechanism. () | |
| dc.type.coar | http://purl.org/coar/version/c_b1a7d7d4d402bcce | |
| dc.type.hasversion | http://purl.org/coar/resource_type/c_7a1f | |
| dc.type.local | Tesis/Trabajo de grado - Monografía - Pregrado | |
| dspace.entity.type | Publication |
Archivos
Bloque original
1 - 3 de 3
Cargando...
- Nombre:
- Carta de autorización.pdf
- Tamaño:
- 509.8 KB
- Formato:
- Adobe Portable Document Format
Cargando...
- Nombre:
- Nota de proyecto.pdf
- Tamaño:
- 176.94 KB
- Formato:
- Adobe Portable Document Format