Investigación de la influencia de la longitud de la zona de condensación y el calor transferido a traves de la mampara sobre la eficiencia térmica de un intercambiador de calor con tubos termosifones aletadas

dc.contributor.advisorPertuz Comas, Alberto David
dc.contributor.advisorCarvajal Mariscal, Ignacio
dc.contributor.authorQuesada Navarro, German Camilo
dc.contributor.authorMartinez Alvarado, Javier Eduardo
dc.date.accessioned2023-04-06T04:21:52Z
dc.date.available2023
dc.date.available2023-04-06T04:21:52Z
dc.date.created2019
dc.date.issued2019
dc.description.abstractEn este artículo, se investiga la aplicación de un intercambiador de calor aire-agua, basado en tubos termosifones en donde se hace fluir, en contra corriente, agua caliente con temperaturas inferiores a 90°C y aire a temperatura ambiente. El intercambiador de calor está conformado por 18 tubos termosifones aletados sin zona adiabática, un área total de intercambio de calor de 12.618 m2 y una relación entre el área del condensador y del evaporador de 2.7037. Se analiza el comportamiento al modificar la relación de áreas (70%Lc-30%Le, 60%Lc-40%Le, 50%Lc-50%Le), el flujo de aire, el caudal y temperatura del agua y al inducir perturbaciones tipo escalonada (2.5-5-7.5 l/min). Es estudiada la influencia que tiene la trasferencia de calor a través de la mampara y de dichas modificaciones sobre la eficiencia del equipo. Se obtiene la configuración más eficiente (=96%) correspondiente a una relación de áreas de 60%Lc-40%Le a una velocidad de 4.2 m/s, un caudal de 10 l/min y una temperatura de 85°C. El calor transferido a través de la mampara Qmamp representa un incremento máximo de 7.19% en la eficiencia del equipo en la configuración anteriormente mencionada. Asimismo, en los perfiles, de temperatura en función del tiempo se observa que, al aumentar el caudal del agua, el sistema tiende a estabilizarse en un menor tiempo y, además, la eficiencia en los nuevos estados estables presentan un máximo decremento de 4.23%. Asimismo, se observa que el tiempo de estabilización, variando únicamente la temperatura del agua a la entrada, es independiente de esta, es decir, el sistema al variar dicha temperatura tiende a estabilizarse a 4.5 min después de iniciada la circulación de los fluidos por el recuperador. *
dc.description.abstractenglishOn this paper, is investigated the aplication of a air-water heat exchanger, based on thermosyphon tubes in where it is flowed, on against flow, hot wáter with temperatures over 90°C and ambient temperature air. The heat exchanger is integrated by 18 finned thermosyphon tubes without adiabatic zone, a total heat exchange area of 12.618 and a relation between the condenser and evaporator area of 2.7037. It is analyzed the behavior over area relations modifications (70%Lc-30%Le, 60%Lc-40%Le, 50%Lc-50%Le), air flow rate and water flow rate and temperature. It is studied the influence that the heat transfer through the bulkhead and the said modification have on the system efficiency. Furthermore, it is analyzed the behavior on the time when it is induced stepped disturbances changing the in-fluid flow (2.5- 5-10 l/min). It is obtained the most efficient configuration (=96%) correspondent to an area relation of 60%Lc-40%Le, an air flow rate of 4.2 m/s, a water flow rate of 10 l/min and a water temperature of 85°C. The heat transferred through the bulkhead represent a maximum increment of 7.19% on the system efficiency on the said configuration. With this is obtained the temperature on time function graphics, where is observe that as the water flow is incremented, the system tends to stabilize on fewer time and, in addition, there is find the efficiency of the new stable states in which the higher decrement is 4.23%. Also, is observe that the stabilization time, just changing the inwater temperature, is independent from this, it means, the system tends to stabilize on 4.5 min after the flow is started through the retriever. *
dc.description.degreelevelPregrado
dc.description.degreenameIngeniero Mecánico
dc.format.mimetypeapplication/pdf
dc.identifier.instnameUniversidad Industrial de Santander
dc.identifier.reponameUniversidad Industrial de Santander
dc.identifier.repourlhttps://noesis.uis.edu.co
dc.identifier.urihttps://noesis.uis.edu.co/handle/20.500.14071/13622
dc.language.isospa
dc.publisherUniversidad Industrial de Santander
dc.publisher.facultyFacultad de Ingenierías Fisicomecánicas
dc.publisher.programIngeniería Mecánica
dc.publisher.schoolEscuela de Ingeniería Mecánica
dc.rightsinfo:eu-repo/semantics/openAccess
dc.rights.accessrightsinfo:eu-repo/semantics/openAccess
dc.rights.coarhttp://purl.org/coar/access_right/c_abf2
dc.rights.creativecommonsAtribución-NoComercial-SinDerivadas 4.0 Internacional (CC BY-NC-ND 4.0)
dc.rights.licenseAttribution-NonCommercial 4.0 International (CC BY-NC 4.0)
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/4.0/
dc.subjectCalor
dc.subjectRecuperador De Calor
dc.subjectTubos Termosifones Bifásicos
dc.subjectEnergía Residual
dc.subjectEficiencia.
dc.subject.keywordHeat
dc.subject.keywordHeat Recover
dc.subject.keywordBiphase Thermosyphon Tubes
dc.subject.keywordResidal Energy
dc.subject.keywordEfficiency.
dc.titleInvestigación de la influencia de la longitud de la zona de condensación y el calor transferido a traves de la mampara sobre la eficiencia térmica de un intercambiador de calor con tubos termosifones aletadas
dc.title.englishInvestigation of the influence of the length of the condensation zone and the heat transferred through the bulkhead on the thermal efficiency of an heat exchanger with finned thermosyphon tubes*.
dc.type.coarhttp://purl.org/coar/version/c_b1a7d7d4d402bcce
dc.type.hasversionhttp://purl.org/coar/resource_type/c_7a1f
dc.type.localTesis/Trabajo de grado - Monografía - Pregrado
dspace.entity.type
Files
Original bundle
Now showing 1 - 3 of 3
No Thumbnail Available
Name:
Carta de autorización.pdf
Size:
172.36 KB
Format:
Adobe Portable Document Format
No Thumbnail Available
Name:
Documento.pdf
Size:
1.16 MB
Format:
Adobe Portable Document Format
No Thumbnail Available
Name:
Nota de proyecto.pdf
Size:
52.48 KB
Format:
Adobe Portable Document Format