dc.description.abstract | La Universidad Industrial de Santander – Sede Barbosa, ofrece una gran variedad de programas educativos como el curso introductorio y ciclo básico para ingenierías, cursos de idiomas, música y educación a distancia, sin embargo por la llegada del covid-19 se identificó la necesidad de adaptar las instalaciones a las aulas híbridas y otras cargas adicionales, lo cual podría sobrecargar el sistema eléctrico actual. Para garantizar la confiabilidad y eficiencia del sistema eléctrico, se realizó un análisis de consumo energético en los tableros generales principales de cada edificio de la universidad, evaluando aspectos como calidad de la energía, balance de cargas, tensión, corriente, potencia activa y reactiva, factor de potencia y cargabilidad del transformador mediante el uso del analizador de redes FLUKE 435 Series II, el cual estuvo conectado por 39 días consecutivos realizando muestreo cada 10 minutos. En la inspección al sistema eléctrico existente se encontraron diferentes tipos de anomalías que presentan un alto riesgo eléctrico para la universidad y su comunidad en general tanto por contacto, protección y mantenimiento como derivaciones realizadas para dar continuidad a circuitos de uso final que llevan mucho tiempo sin dar solución alguna, empalmes mal elaborados, saturación de los barrajes en los tableros, conductores quemados, bornes de protecciones sulfatadas, entre otras. | |
dc.description.abstractenglish | The Industrial University of Santander – Barbosa Campus, offers a wide variety of educational programs such as the introductory course and basic cycle for engineering, language courses, music and distance education, however, due to the arrival of covid-19, the need to adapt facilities to hybrid classrooms and other additional loads, which could overload the current electrical system. To guarantee the reliability and efficiency of the electrical system, an energy consumption analysis was carried out on the main general Electrical panel of each university building, evaluating aspects such as energy quality, load balance, voltage, current, active and reactive power, power factor and loadability of the transformer through the use of the FLUKE 435 Series II network analyzer, which was connected for 39 consecutive days, sampling every 10 minutes. In the inspection of the existing electrical system, different types of anomalies were found that present a high electrical risk for the university and its community in general, both due to contact, protection and maintenance and derivations made to provide continuity to end-use circuits that have been without for a long time. Provide any solution, poorly made splices, saturation of the bars in the panels, burned conductors, sulfated protection terminals, among others. | |
dc.description.degreelevel | Pregrado | |
dc.description.degreename | Ingeniero Electricista | |
dc.format.mimetype | application/pdf | |
dc.identifier.instname | Universidad Industrial de Santander | |
dc.identifier.reponame | Universidad Industrial de Santander | |
dc.identifier.repourl | https://noesis.uis.edu.co | |
dc.identifier.uri | https://noesis.uis.edu.co/handle/20.500.14071/42409 | |
dc.language.iso | spa | |
dc.publisher | Universidad Industrial de Santander | |
dc.publisher.faculty | Facultad de Ingeníerias Fisicomecánicas | |
dc.publisher.program | Ingeniería Eléctrica | |
dc.publisher.school | Escuela de Ingenierías Eléctrica, Electrónica y Telecomunicaciones | |
dc.rights | info:eu-repo/semantics/openAccess | |
dc.rights.accessrights | info:eu-repo/semantics/openAccess | |
dc.rights.coar | http://purl.org/coar/access_right/c_abf2 | |
dc.rights.creativecommons | Atribución-NoComercial-SinDerivadas 4.0 Internacional (CC BY-NC-ND 4.0) | |
dc.rights.license | Atribución-NoComercial-SinDerivadas 2.5 Colombia (CC BY-NC-ND 2.5 CO) | |
dc.rights.uri | http://creativecommons.org/licenses/by-nc-nd/4.0/ | |
dc.subject | Consumo energético | |
dc.subject | Calidad de la energía | |
dc.subject | Cargabilidad | |
dc.subject | Eficiencia energética | |
dc.subject.keyword | Energy consumption | |
dc.subject.keyword | Energy quality | |
dc.subject.keyword | Loading capacity | |
dc.subject.keyword | Energy efficiency | |
dc.title | Caracterización de la demanda existente y parámetros de la calidad de la energía del transformador eléctrico principal de la universidad industrial de Santander – sede Barbosa | |
dc.title.english | Characterization of the existing demand and energy quality parameters of the main Electrical transformer of the Industrial University of Santander – Barbosa campus | |
dc.type.coar | http://purl.org/coar/resource_type/c_7a1f | |
dc.type.hasversion | http://purl.org/coar/version/c_b1a7d7d4d402bcce | |
dc.type.local | Tesis/Trabajo de grado - Monografía - Pregrado |
Files
Original bundle
1 - 4 of 4
No Thumbnail Available
- Name:
- Nota de proyecto.pdf
- Size:
- 102.94 KB
- Format:
- Adobe Portable Document Format
No Thumbnail Available
- Name:
- Carta de autorización.pdf
- Size:
- 178.96 KB
- Format:
- Adobe Portable Document Format
License bundle
1 - 1 of 1
No Thumbnail Available
- Name:
- license.txt
- Size:
- 2.18 KB
- Format:
- Item-specific license agreed to upon submission
- Description: